4–1
SECTION 4
Basic Hardwired Zones 1–8
••••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
Installing the Hardwired Zones
Keyswitch Installation
Programming Hardwired Zones
Checkout Procedure for Hardwired Zones
••••••••••••••••••••••••••••••••••••••••••••••••••
Installing the Hardwired Zones
Common Characteristics of Zones 1–8
•EOLR-
supervised
zones support both open-circuit and closed-circuit devices.
•As
many
4-wire smoke detectors
as can be powered from Aux Power on the control (zones
2–7).
Programmable
for 10, 350, or 700mSec response.
350mSec (default) should be used for most standard contacts. For vibration-type contacts,
10mSec is more suitable.
Wiring Burglary and Panic Devices to Zones 1–8
To wire burglary and panic devices to zones 1-8, perform the following steps, referring to
Figure 24. SL150 Summary of Connections
at the back of this manual.
1.
Connect sensors/contacts to the hardwired zone terminals (8 through 20).
2.
Connect closed-circuit devices in series in the high (+) side loop. The EOL resistor must
be connected in series with the devices, following the last device.
3.
Connect open-circuit devices in parallel across the loop. The 2000-ohm EOLR must be
connected across the loop wires at the last device.
If the EOLR is not at the end of the loop, the zone will not be properly supervised, and the system
may not respond to an open-circuit on the zone.
High-Resistance/Short Supervision on Hardwired Zones 2–8
Special supervision in the control panel senses high resistance or a short on hardwired loops
2–8, causing a display of “CHECK” along with the number of the affected zone when the
system is in the disarmed state. The system cannot be armed when this condition is present.
If the system is armed when a high-resistance or short condition occurs, no display will take
place until the system is disarmed.
Wiring 2-Wire Smoke Detectors to Zone 1
1. Connect 2-wire smoke detectors across zone 1 terminals 8 (+) and 9 (–). Observe proper
polarity when connecting the detectors.