SL150 Installation and Setup Guide
1–4
Dynamic Signaling Feature
This control features Dynamic Signaling Delay and Dynamic Signaling Priority
message reporting when Long Range Radio is used. This feature, which is
programmed in data fields
✱
54 and
✱
55, is designed to reduce the number of
redundant reports sent to the central station. Field
✱
29, OUTPUT TO LONG
RANGE RADIO, must be enabled for this feature to function.
Alarm Output
• Provides a 12VDC, 2
amp
output that can drive the compatible sounders listed in
Section 9:
External Sounders
(assuming a fully charged battery is connected).
• Steady output for burglary/panic, or
temporal
pulse output (3 pulses – pause – 3
pulses – pause – 3 pulses . . .) for fire.
• Uses
current
-limiting circuitry for protection.
Auxiliary Power Output
• Provides 12VDC, 600mA maximum (500mA max for UL installations). Uses
current-limiting circuitry for protection.
• Interrupts for smoke detector reset if 4-wire smoke detectors are used.
Programming
Programmed options are stored in electrically erasable, nonvolatile EEPROM
memory (information can be reprogrammed at any time and will not be lost in the
event of a power loss).
The system can be uploaded, downloaded, or controlled via an IBM-compatible
computer, ADEMCO
COMPASS
®
software, and a
modem specified by ADEMCO.
Keypad programming consists of:
• Data field programming
• Interactive (menu) mode programming
To program from a keypad, you must connect an SL6160 (2-line alpha keypad), but it need not
stay in the system.
Communication Formats Supported
• Ademco Low Speed (Standard or Expanded)
• Sescoa/Radionics (Standard or Expanded)
• Ademco Express
•Ademco
Contact ID.
Zone Descriptors
You can assign alpha descriptors to all zones (only when using alpha keypads and/or
the 4285/4286 VIP Module).
AC Power Supply
Uses
1321
, 110VAC plug-in transformer with 16.5VAC 25VA output, unless
Powerline Carrier devices
(for example,
X10 type) are used, in which case a 4300
Transformer Module
must be used.
Backup Battery
Rechargeable (Sealed Lead Acid) 12VDC, 4AH minimum. The actual battery size
needed can be determined by using the formula found in Section 12,
FINAL POWER-
UP
(see “Calculating the Battery Size Needed”).