SECTION 24
Testing the System
••••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
Test Procedure
••••••••••••••••••••••••••••••••••••••••••••••••••
Test Procedure
After installation is completed, the security system should be carefully tested, as follows.
1. With the system in the disarmed state, check that all zones are intact. If a
NOT
READY
message is displayed, press [
] to display the faulted zone(s). Restore faulted zone(s) if
necessary, so that the
SYSTEM
READY
message
is displayed. Fault and restore every
sensor individually to assure that it is being monitored by the system.
2. Enter the 4-digit Security code and press the TEST [
5
]
key. The outside sounder will
sound for 1 second. The keypad should sound 3 beeps each time a contact is faulted. A
"Test"
report
Error! Bookmark not defined.
is transmitted (if programmed) to the
Central Station immediately. If the backup battery is discharged or missing, the sounder
may not turn on and a
"Low Battery"
report will be transmitted with a
"Test"
report.
The keypad will beep once every 30–35 seconds as a reminder that the system is in the
Test mode.
To turn off the Test mode, enter 4-digit Security code and press the OFF [
1
] key.
NOTE:
Triggering a zone set to
Arm AWAY
,
Arm STAY
, or
Disarm
will take the system
out of Test mode and cause that action.
Alarm messages will be sent to the Central Station during tests 3 and 4, below.
Notify Central Station personnel in advance that tests will be in progress.
3. Arm the system and fault one or more zones. After 15 seconds (if Optional Dialer Delay is
selected), silence alarm sounder(s) by entering the
Security code
and pressing OFF key.
Check entry/exit delay zones.
4. Check the keypad-initiated alarms that are in the system by pressing the appropriate
PANIC key pairs. If the system has been programmed for audible emergency, the keypad
will emit a
steady
alarm sound, and
ALARM
and zone number will be displayed. Silence
the alarm by entering the
Security code
and pressing OFF key.
If the system has been programmed for Silent Emergency, there will be no audible alarms
or displays, but a report will be sent to the Central Station.
5. If output Relay Units/Powerline Carrier devices have been installed, test their
programmed action.
6 Notify Central Station personnel when all tests are finished, and verify results with them.
7. To test the wireless part of the system and the RF receiver, perform the following two
additional tests: